Series-C I/O modules are constructed to support normal field failures, wiring errors and conditions such as a shorted wire. All Series-C IOTAs contain at least one fuse that provides protection for catastrophic errors in the IOTA, IOM and other elements of the Series-C system. In normal operation as well as many abnormal operations, the fuse element should not blow.
INQUIRE NOW
Products Name: 30752787-002 Honeywell Programmable controller Brand new
PRODUCT DESCRIPTION
Brand: Honeywell
Model number:30752787-002
Colour:new
Warranty: 12 months
Lead Time:3-day working day
Country of origin: USA Price: Please contact us
Product weight:0.5kg
Shipping Port: China
Payment: Bank of Chicago, Bank of Singapore
Express cooperation: fedex, DHL, UPS and your express account
Service : Professional Sales provides 24 hours /7 days online service
30752787-002 Honeywell Programmable controller Brand new
Description:
You have logged onto Control Builder with sufficient security level to make control strategy
changes.
l You can remove and install the Series C IOM under power.
l Be sure you take ESD hazard precautions when handling the module and IOTA.
16.3.2 To replace an I/O module
1. Loosen the screws:
l at each side of the plastic cover that secures the I/O module to the IOTA board, and
l the long gray plastic screw located on the module's face. It is not necessary to completely
remove this screw.
CAUTION
Only use a #2 Phillips screwdriver to carefully loosen or tighten the long gray plastic
screw. Do not use either a #1 Phillips screwdriver or a battery-powered screwdriver
to remove or install the plastic screw as this can damage the screw head.
2. Remove the I/O module from the IOTA board and connector.
3. Insert the new I/O module onto IOTA board making sure that the I/O circuit board mates
properly with the IOTA board connector.
4. Secure the module to the:
l IOTA board
using the two metal screws at the plastic cover
tightening the long gray plastic screw. See CAUTION in Step 1.
l Carrier - with the long screw that is inserted into the hole on the face of the module's
plastic cover.
The new I/O module boots-up to the IDLE state.
5. Load firmware which is the same version as was running in the old controller.
6. In Control Builder, perform a 'Load with Contents".
Shipping Port: China
Payment: Bank of Chicago, Bank of Singapore
Express cooperation: fedex, DHL, UPS and your express account
Service: Professional Sales provides 24 hours /7 days online service
Related products:
TC-IXL062
TC-KIOL02
TCM4351A
TCM4351B
TC-OAH061
TC-ODD32
TC-ODX161
TCP202A
TC-RPFM01
TCSECE300R2
TCSEK3MR10
TC-TG-F1C3
TC-XXXXX2
The winter solstice is Du 1 of the four solar terms of 20 Bai, and ...
Dec. 18 , 2020Let's first take a look at the literal meaning of the DCS system.
Dec. 24 , 2020