The MS/TP MAC address for each device must be set to a
unique value in the range of 0-127 on an MS/TP network
segment. DIP switches on the Spyder BACnet controller
are used to set the controller's MAC address.
INQUIRE NOW
Products Name: 51402645-200 Honeywell Controller module Brand new
PRODUCT DESCRIPTION
Brand: Honeywell
Model number:51402645-200
Colour:new
Warranty: 12 months
Lead Time:3-day working day
Country of origin: USA Price: Please contact us
Product weight:0.5kg
Shipping Port: China
Payment: Bank of Chicago, Bank of Singapore
Express cooperation: fedex, DHL, UPS and your express account
Service : Professional Sales provides 24 hours /7 days online service
51402645-200 Honeywell Controller module Brand new
Description:
Examine the AC power cord for the power supply and then check if there is any splits or cracks
in the insulation.
2. Replace power cord if needed.
NOTE
If the bulk supplies are wired directly to circuit breakers, then special permits may
be required for replacing the cord.
3. (If present) Check the condition of MOV’s installed for cracks and/or burn spots in the devices
and then replace if needed.
4. Measure the AC input voltage and record the value.
5. (If UPS power is used) Check the quality of the AC waveform (that is, ensure that the waveform
is within manufacturer’s specifications).
Distortion:
Utility mains power normally has less than 5 % harmonic distortion.
Transformer of proper rating adds about 1 % distortion.
Total Harmonic Distortion (THD) of 6 % is acceptable.
Maximum THD acceptable is 8 %.
6. Check the red and black DC power wires connected to each power supply for
l signs of corrosion in the power wires,
l splits or cracks in the insulation, and
l loose connections on each end of the wires.
7. Inspect the red and black DC power wires connected between each cabinet (in a cabinet
complex) for
l signs of corrosion in the power wires connected between each cabinet,
l splits or cracks in the insulation, and
l connection of wires to the connector blocks.
8. Inspect the ground wire for AC Safety Ground exiting the cabinet for
l signs of corrosion in the ground wire,
l splits or cracks in the insulation, and
l loose connections at each end of the wire.
9. Inspect whether a 4 AWG (5.3 mm) or larger wire is used to connect
l AC Safety Ground in the cabinet to the AC Safety Ground collection plate, and
l AC Safety Ground to the AC Safety Ground rod.
Inspect how the wire from AC Safety Ground in the cabinet routed to the AC Safety Ground
collection plate.
10. a. Inspect the ground wire for MRG.
b. Inspect whether a 4 AWG (5.3 mm) or larger wire used to connect the local reference bar
with the MRG ground rod.
c. Check for loose connections at each end of the wire
Shipping Port: China
Payment: Bank of Chicago, Bank of Singapore
Express cooperation: fedex, DHL, UPS and your express account
Service: Professional Sales provides 24 hours /7 days online service
Related products:
TC-IXL062
TC-KIOL02
TCM4351A
TCM4351B
TC-OAH061
TC-ODD32
TC-ODX161
TCP202A
TC-RPFM01
TCSECE300R2
TCSEK3MR10
TC-TG-F1C3
TC-XXXXX2
The winter solstice is Du 1 of the four solar terms of 20 Bai, and ...
Dec. 18 , 2020Let's first take a look at the literal meaning of the DCS system.
Dec. 24 , 2020