INQUIRE NOW
Products Name: 6EQ1131-1AF00-0BA0 Siemens communication module
PRODUCT DESCRIPTION
Brand:siemens
Model number:6EQ1131-1AF00-0BA0
Colour:new
Warranty: 12 months
Lead Time:3-day working day
Country of origin: USA Price: Please contact us
Product weight:0.35kg
Shipping Port: Xiamen, China
Payment: Bank of Chicago, Bank of Singapore
Express cooperation: fedex, DHL, UPS and your express account
Service: Professional Sales provides 24 hours /7 days online service
Description:
Two fully compatible versions:
– TXM1.8U: 8 inputs/outputs with LED signal / fault indication
– TXM1.8U-ML: As TXM1.8U, but with additional local override facility
with LCD display (LO/ID to ISO 16 484-2)
• 8 universal I/O points, individually configurable as
– Digital input: maintained contact, pulse or counter
– Analog input: sensor, 0..10V
– Analog output: 0..10V
• Compact DIN format, small footprint
• Separate terminal base and plug-in I/O module for convenient handling
– Self-establishing bus connection for maximum ease of installation
– Terminal isolation function for fast commissioning
– I/O module replaceable in seconds, without rewiring and without affecting
the full functioning of the remaining I/O modules
• All terminals are directly on the I/O modules, allowing direct connection of
field devices without additional terminal strips.
• Simple strategy for operation and display
– I/O status LED for each I/O point; mode of operation (N/C or N/O) and
brightness depend on I/O function
– LEDs and LCD for fast diagnostics
• Double-sided labels for identification of all I/O points
For a detailed description, please refer to document CM110561, "TX-I/O™ Functions
and operation".
• Pressing an override button in the middle enables or disables the local override
• Pressing "+" or "–" respectively increases or reduces the output value.
• Only outputs can be overwritten. Any attempt to overwrite an input results in an error
indication.
• The yellow "Override" LED indicates that local override is active
• The following information is displayed for each I/O point:
– Configured signal type
– Symbolic display of process value
– Information for diagnostics.
• All safety-relevant functions must be implemented with external solutions
• The local override must not be used for safety shutdown operations
• In compliance with the standard (ISO 16 484-2, Section 3.110), the module
executes all local overrides directly, without safety precautions or interlocks.
Full responsibility lies with the operator.
Shipping Port: Xiamen, China
Payment: Bank of Chicago, Bank of Singapore
Express cooperation: fedex, DHL, UPS and your express account
Service: Professional Sales provides 24 hours /7 days online service
Relevant details:
1FT5066-0AK71-1-Z
3TK2827-1AJ20
3TY7561-1A
6ED7193-4CF50-0AA0
6EP1332-1SH12
6ES7132-4BD32-0AA0
6ES7193-4CD30-0AA0
6ES7214-1AC01-0XB0
6ES7810-5CC10-0YR5
6DR2800-8J
6ES7214-1BD23-0XB8
The winter solstice is Du 1 of the four solar terms of 20 Bai, and ...
Dec. 18 , 2020Let's first take a look at the literal meaning of the DCS system.
Dec. 24 , 2020