If a moderate percentage of non-permanent faults is present in a system, two or more shots are justified. If fused ‘tees’ are used and the fault level is low, the timer of the fuses may not discriminate with the main IDMT relay: several shots are usefull. This would not warm up the 

fuse to a such extent that it would eventually blow before the main protection operated.

Description:

 Overload Relays
Thermal overload relays sense motor current by 
converting this current to heat in a resistance 
element. The heat generated is used to open a 
normally closed contact in series with a starter 
coil causing the motor to be disconnected from 
the line.
In spite of being relatively simple and inexpensive, 
thermal overload relays are very effective in 
providing motor running overcurrent protection. 
This is possible because the most vulnerable part 
of most motors is the winding insulation and this 
insulation is very susceptible to damage by 
excessively high temperature.
Being a thermal model of a motor, the thermal 
overload relay will produce a shorter trip time at a 
higher current similar to the way a motor will reach 
its temperature limit in a shorter time at a higher 
current. Similarly, in a high ambient temperature, 
a thermal overload relay will trip at a lower current 
or vice versa allowing the motor to be used to its 
maximum capacity in its particular ambient 
temperature (if the motor and the overload are in 
the same ambient).
 1998 Square D All Rights Reserved
12
5/98
Thermal Overload Relays – NEMA Rated
Application Data
Once tripped, the thermal overload relay will not 
reset until it has cooled, automatically allowing the 
motor to cool before it can be re-started.
Square D manufactures two basic types of 
thermal overload relays, the melting alloy and the 
bimetallic. In some types, the bimetallic is 
available in both non-compensated and ambient 
temperature-compensated versions. In both 
melting alloy and bimetallic, single element and 
three element overloads are available.
Motor Logic Solid State overload relays use an 
electronic method of detection, which responds 
directly to the motor current. When tripped the 
overload relay may be reset either manually or 
remotely using the Remote Reset Module. The 
Solid State overload relay provides overload 
protection only for three phase motors rated up to 
600 volts AC.
The Solid State overload relay provides protection 
for phase loss and phase unbalance. In addition, 
this overload relay is ambient insensitive. The 
Solid State overload relay is available as a 
separate trip Class 10 or 20 and as a selectable 
trip Class 10/20 device.
The Motor Logic solid state overload relay must 
be selected based on the FLA of the motor it is to 
protect. Applications involving a motor with an 
FLA less than 1.5 amps can be addressed by 
passing multiple looped turns of the motor leads 
through the current transformer windows. 


AS-J890-000   SCHNEIDER

Shipping Port: Xiamen, China

Payment: Bank of Chicago, Bank of Singapore

Express cooperation: fedex, DHL, UPS and your express account

Service: Professional Sales provides 24 hours /7 days online service

image.png

Related products:

2704

140CRA93200

170ADM35010

170LNT71000

BMEH584040C

HMIGTO4310 

TM221C24T

TSXCUSBMBP

170ENT11002

140CPU67160S

170NEF11021

140cps11420

140aci04000

140aco02000

140NOE77101

DAP212

LMC101CAA10000