Brand: WoodWard
Model number:5501-365
Colour:new
Warranty: 12 months
Lead Time:3-day working day
Country of origin: USA Price: Please contact us
Product weight:0.85kg
Shipping Port: China
Payment: Bank of Chicago, Bank of Singapore
Express cooperation: fedex, DHL, UPS and your express account
Service: Professional Sales provides 24 hours /7 days online service
5501-365 WOODWARD
INQUIRE NOW
Products Name: 5501-365 WOODWARD
PRODUCT DESCRIPTION
Do NOT use the minimum-fuel contact as a part of any emergency stop sequence. The emergency may be caused by a governor malfunction which would also cause a malfunction of the minimumfuel feature. Use of the minimum-fuel contact for an emergency stop sequence could cause overspeed of the prime mover and mechanical
damage and personal injury, including death.
Benefits:
With the prime mover operating at rated speed and no load, record the voltage
across the actuator terminals 9 (+) and 10 (–). Shut down the prime mover and
activate the Failed Speed Signal Override by closing the override contact. The
voltage to the actuator should now be adjustable by the START FUEL LIMIT
potentiometer. Set the actuator voltage about 30% higher than the voltage
obtained at rated speed for forward-acting controls and 30% lower than rated
speed voltage for reverse-acting controls. Remove the Failed Speed Signal
Override contact if not required to start the prime mover.
Start the prime mover and observe the start time, overshoot of speed setting, and
exhaust smoke obtained. If the prime mover does not start, turn the START
FUEL LIMIT potentiometer slightly clockwise until the prime mover starts. The
START FUEL LIMIT may be adjusted as required to optimize the prime-mover
starting characteristics. The fuel-limiting function is turned off automatically when
the speed control takes over.
For prime movers not requiring start-fuel limiting, the START FUEL
LIMIT function can be deactivated by turning the potentiometer fully
clockwise (be careful not to overtorque the pot).
Speed Sensor Check
If the sensor is a magnetic pickup, measure the voltage across terminals 7 and 8
to be sure there is a minimum of 1.0 volts at cranking speed, and a maximum of
30 Vrms at rated speed. If the voltage exceeds 30 volts, increase the gap of the
speed sensor, and be sure that there is still a minimum of 1.0 volts at cranking
speed.
Droop Adjustment
The amount of droop is not critical in many installations. If the engine needs to
run in droop but the amount is not critical set the droop potentiometer in midposition, then adjust load with the speed-setting potentiometer.
When paralleled with an infinite bus, the generator frequency cannot change, and
unless a load- sensing module is being used, the control must be in droop to
maintain stable operation. With the droop potentiometer at mid-position, parallel
the generator, then increase the Rated Speed potentiometer until the desired
amount of load on the engine is achieved.
Too much droop will cause the engine to overspeed should the load be suddenly
lost. Excessive droop will also cause the engine to be sluggish in response to
load changes.
Shipping Port: China
Payment: Bank of Chicago, Bank of Singapore
Express cooperation: fedex, DHL, UPS and your express account
Service: Professional Sales provides 24 hours /7 days online service
Related products:
9907-018
DSS-2
5464-643
5466-031
5466-253
5466-258
5466-348
5466-353
5501-367
5501-376
5464-658
5466-409
9907-838
9907-014
9905-131
9907-186
9907-414
9907-838
9970-164
5441-413
9905-003
505-4532
8200-224
1247-007
1326-183
1355-169
5210-543
5464-551
8250-565
8290-195
8405-307
8406-113
The winter solstice is Du 1 of the four solar terms of 20 Bai, and ...
Dec. 18 , 2020Let's first take a look at the literal meaning of the DCS system.
Dec. 24 , 2020